Feed/CVE-2022-33174
CVE-2022-33174CRITICALCVSS 9.8

CVE-2022-33174

Published Jun 13, 2022·Updated Jun 16, 2026

NVD Description

Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

Public Exploits & PoCs1 found

CVSS Vector

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

References

View on NVD Search GitHub Search Google

Get alerted for CVEs like this

Register your stack and get notified within minutes when a matching CVE drops.